Operational Report 2008

Apr 22, 2020

SYSTEM PROCEDURE MONTHLY STATUS REPORT

MILLTOWN APRIL 2008

External Analysis of Final Treated Water

Laboratory Name: Euro Environmental Services

Report No. : 5110/380/02

Date Of Sample:10/04/2008

Date of Report: 28/04/2008

Analysis Results for Treated Water

Parameter

Results

Unit

Limit

Aluminium

Not Used as a coagulant. Therefore not tested.

Ammonia

0.26

mg.l as N

0.3

Colour (apparent)

11

PtCo Units

20

Colour (true)

<3.9

PtCo Units

20

Conductivity

1646

uS/cm at 20C 2500

 

Hydrogen ion conc.

7.4

pH Units

6 to 9

Iron

<3.7

ug/L

200

Manganese

1

ug/L

50

Nitrate

<0.09

mg/L

11.3

Nitrite

0.054

mg/L

0.5

Odour

Compliant to consumer as no complaints

were received this reporting period.

Taste

Turbidity

0.07

NTU

1

 

 

SYSTEM PROCEDURE MONTHLY STATUS REPORT

MILLTOWN MAY 2008

External Analysis of Final Treated Water

Laboratory Name: Euro Environmental Services

Report No. : 5110/409/02

Date Of Sample:17/05/2008

Date of Report: 28/05/2008

Analysis Results for Treated Water

Parameter

Results

Unit

Limit

Aluminium

Not Used as a coagulant. Therefore not tested.

Ammonia

0.24

mg.l as N

0.3

Colour (apparent)

<3.9

PtCo Units

20

Colour (true)

<3.9

PtCo Units

20

Conductivity

1589

uS/cm at 20C

2500

Hydrogen ion conc.

7.4

pH Units

6 to 9

Iron

5

ug/L

200

Manganese

1

ug/L

50

Nitrate